For residential, LULA and low flow applications.
- This information is provided with the understanding that it is only to be used by qualified hydraulic elevator professionals.
- Optimum oil temperature for adjusting valve is 80°F (27°C) min. to 100°F (38°C) maximum.
- Each new valve is adjusted to a set of standard conditions at the factory. You only need to adjust DM and BP settings. Other minor adjustments may be required to suit your application. Final adjustments are made 1/8 turn (or less) at a time for optimum performance.
- After valve adjustments are finalized, snug tighten lock nuts (DO NOT over tighten).
- Valve must be mounted with the solenoids in a vertical position. 5 inches (127mm) minimum clearance is required to remove the valve cover for service.
- When disconnecting solenoids, do it electrically, not physically.
- It is important to keep system oil clean. EECO recommends the use of a 5-micron filtration system.
- If DC requires further adjustment, first preset DA, adjust DC as required, then readjust DA.
- DO NOT adjust the valve to suit switches (vanes/magnets). Adjust the switches to suit the valve. Recommended slowdown distance is 2 in. for every 10 fpm of car speed.
(U1 - Up Fast solenoid / U2 - Up Slow solenoid)
- BP Bypass - Car at lower floor with no load. Disconnect U2. Register an up call. Turn BP CW until car moves, then CCW until car stalls plus 1/2 turn. Stop pump motor and reconnect U2.
- UA Up Acceleration - Car at lower floor with no load. Register an up call and observe up acceleration. Turn UA a small step at a time CCW for faster or CW for slower up acceleration. DO NOT drag out acceleration.
- UL Up Leveling - Car at lower floor with no load. Disconnect U1. Register an up call. Turn UL CW (faster) or CCW (slower) to set up leveling speed at 9 to 12 fpm (.05 to .06 m/s). Leave U1 disconnected.
- UT Up Transition - Car at lower floor with no load. Register an up call. The car will move up at leveling speed. Turn UT CW until car speeds up, then slowly CCW until car slows down to leveling speed again. Reconnect U1. Cycle car and observe up transition. Turn UT CW for slower transition or CCW for faster transition. Slowdown switch should be set to give 3 to 4 inches (75 mm to 100 mm) of stabilized leveling.
- US Up Stop - Car at lower floor with no load. Disconnect U2. Register an up call. The car should not move. Turn US CW until car moves then slowly CCW until the car stops again. Reconnect U2. Cycle car and observe up stop. Turn US CW for softer stop or CCW for firmer stop. NOTE: Pump motor must run approximately 1 second after the car has stopped.
CW = Clockwise (IN)
CCW = Counter Clockwise (OUT)
BP Bypass
CCW to stop. (CCW - Delays up start)
UA Up Acceleration
Flush to locknut, CCW 9 turns. (CCW - Faster)
UL Up Leveling
CW to stop then CCW 5 turns. (CW - Faster speed)
UT Up Transition
CCW to stop. (CW - Slower transition)
US Up Stop
CCW to stop. (CW - Softer stop)
RV Relief Valve
Factory set at 550 psi (38 bar). (CW - Increase pressure setting)
CW = Clockwise (IN)
CCW = Counter Clockwise (OUT)
DL Down Leveling
CCW to stop then CW 6 turns. (CW - Slower speed)
DM Down Main
CW to stop then CCW 6 turns. (CW - Slower speed)
DC Down Closing
CCW to stop, then CW * turns. (CW - Softer Stop)
*Previous to Serial # 1R18N0028, CW 15 turns – Serial # 1R18N0028 or later, 4 CW turns
DT Down Transition
CW to stop. (CCW - Slower transition)
DA Down Acceleration
CCW to stop. (CW - Slower acceleration)
DSC Down Speed Control
CCW to stop. (CW - Slower down speed - full load)
ML Manual Lowering
CW to stop. (CCW - Opens valve)
Sequence of Operations
All Valves
Up Start:
- “ATL” (Across The Line) start: pump motor “ON”. Energize both U2 and U1 solenoids to run up at fast speed.
- "Wye" start: Pump motor “ON” (reduced voltage). “Delta” run: Pump motor “ON” full voltage. Energize both U2 and U1 solenoids to run up at fast speed. De-energize U1 to slowdown to leveling speed. De-energize U2 to stop at the floor.
CAUTION: Never energize U2 and U1 during "Wye" start, only after “Delta” run!
Down Start:
- Energize D1 and D2 to lower the car at fast speed. De-energize D1 to slowdown to leveling speed. De-energize D2 to stop at the floor.
Note: Pump motor must be timed to run approximately 1 second after the car has stopped.